The FCI 7100 series fire alarm control panel is a multi-processor-based, analog addressable system in a compact, yet expandable, platform. Intended for commercial, industrial and institutional installations, it. is ideal for life safety and property protection applications. The basic 7100 series control panel provides two analog addressable signaling line circuits (SLCs). Each SLC supports up to 99 analog addressable sensors, as well as up to 99 addressable monitor modules and/or control points. With 198 addresses available on each SLC, total system capacity reaches 396 addresses. The 7100 uses an advanced protocol that ensures an almost instant response to events while at the same time suppressing nuisance alarms.

The system may be programmed with either the Windows®-based Field Configuration Program (FCP-7100) or through a comprehensive set of intuitive, securely password protected front-panel programming options. This important feature allows the system to quickly adapt to any future requirements brought on by changes in occupancies, building remodelings, or other contingencies.

The sophisticated circuitry and powerful analog software enables the 7100 series fire alarm control panel to read the specific sensitivity level of each sensor and compensate for any changes due to age, dust accumulation or other environmental factors. The 7100 incorporates the FCI Listed Integrated Sensitivity Testing (LIST) which meets NFPA 72 sensitivity testing and maintenance requirements. The LIST testing allows substantial savings in both maintenance and service while virtually eliminating nuisance alarms.

The Model 7100-2D (non-FM) features an integral Digital Alarm Communicator Transmitter (DACT) with all popular transmission formats and a 16-digit telephone number field. It is 8-digit Carrier Information Code (CIC) compliant and also prevents dialer-runaway in the event of intermittent system faults. The 7100-2D is UL Listed for Remote Station, Proprietary, and Central Station fire alarm systems.

The 7100 is housed in an attractive, contemporary styled cabinet. It allows ample space for wiring and room for batteries up to 7A/H capacity.

Features:

  • Integral Digital Alarm Communicator (with the 7100-2D)
  • 120 or 24O VAC (optional) Input Line Voltage
  • 80.character Alpha-numeric Display Two Style 4 (Class "B") Signaling Line Circuits. Style 6 (Class "A ") with optional CAOM module
  • Two Style Y (Class "B") Regulated Notification Appliance Circuits rated for 1.5 Amp. each. Style Z (Class "A") with optional CAOM module
  • Suitable for Pre-Action Deluge applications with optional MCOM module
  • Intuitive Front Panel Programming
  • Periodic Trouble Reminder
  • Individual Sensor Drift Compensation
  • Listed Integral Sensitivity Testing (LIST)
  • Dual-stage Maintenance alerts ("Dirty" and "Very Dirty")
  • Multi-level Sensor Sensitivity Adjustments (Front Panel programmable)
  • Day/Night Sensitivity Adjustments (Front Panel programmable)
  • Alarm Verification per Individual Sensor
  • Positive Alarm Sequence for Sensors or Monitor Modules
  • Four Levels of System Access using Six Digit Passwords with up to Five User Passwords per Level
  • Duplicate and Extra Address indications
  • March Time (60 or 120 BPM)/ Temporal Pattern/ Coded Fours/ California Code
  • User-Defined Zone Coding
  • Cross Zoning
  • 500 Event Log
  • Fan Restart with Sequential Restart Delay
  • Upload/Download of Panel Configuration between Panel and FCP-7100 program (Password protected feature)
  • Up to 64 7100 panels in NetSOLO® network with optional INI-7100 module
 
 